Filtered by vendor Siemens
Subscribe
Total
2135 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2014-2259 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | 7.8 HIGH | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTPS packets. | |||||
| CVE-2016-4784 | 1 Siemens | 9 Siprotec 4 En100, Siprotec Compact Model 7rw80, Siprotec Compact Model 7sd80 and 6 more | 2025-04-12 | 5.0 MEDIUM | 5.3 MEDIUM |
| A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.83; SIPROTEC 7UT686 : All versions < V 4.01; SIPROTEC 7SD686 : All versions < V 4.03; SIPROTEC 7SJ66 : All versions < V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained. | |||||
| CVE-2015-1597 | 1 Siemens | 1 Spcanywhere | 2025-04-12 | 6.8 MEDIUM | N/A |
| The Siemens SPCanywhere application for Android does not use encryption during the loading of code, which allows man-in-the-middle attackers to execute arbitrary code by modifying the client-server data stream. | |||||
| CVE-2015-1595 | 1 Siemens | 1 Spcanywhere | 2025-04-12 | 4.3 MEDIUM | N/A |
| The Siemens SPCanywhere application for Android and iOS does not use encryption during lookups of system ID to IP address mappings, which allows man-in-the-middle attackers to discover alarm IP addresses and spoof servers by intercepting the client-server data stream. | |||||
| CVE-2015-5374 | 1 Siemens | 3 Siprotec 4, Siprotec Compact, Siprotec Firmware | 2025-04-12 | 7.8 HIGH | N/A |
| A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device. | |||||
| CVE-2016-1488 | 1 Siemens | 4 Ozw672, Ozw672 Firmware, Ozw772 and 1 more | 2025-04-12 | 4.3 MEDIUM | 6.1 MEDIUM |
| Cross-site scripting (XSS) vulnerability in the login form in the integrated web server on Siemens OZW OZW672 devices before 6.00 and OZW772 devices before 6.00 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. | |||||
| CVE-2016-8673 | 1 Siemens | 8 Simatic Cp 343-1, Simatic Cp 343-1 Firmware, Simatic Cp 443-1 and 5 more | 2025-04-12 | 6.8 MEDIUM | 8.8 HIGH |
| A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server at port 80/TCP or port 443/TCP of the affected devices could allow remote attackers to perform actions with the permissions of an authenticated user, provided the targeted user has an active session and is induced to trigger the malicious request. | |||||
| CVE-2016-8563 | 1 Siemens | 1 Automation License Manager | 2025-04-12 | 5.0 MEDIUM | 7.5 HIGH |
| Siemens Automation License Manager (ALM) before 5.3 SP3 Update 1 allows remote attackers to cause a denial of service (ALM service outage) via crafted packets to TCP port 4410. | |||||
| CVE-2014-4683 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | 4.9 MEDIUM | N/A |
| The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a (1) HTTP or (2) HTTPS request. | |||||
| CVE-2014-2248 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | 4.3 MEDIUM | N/A |
| Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. | |||||
| CVE-2015-1602 | 1 Siemens | 1 Simatic Step 7 | 2025-04-12 | 2.1 LOW | N/A |
| Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 improperly stores password data within project files, which makes it easier for local users to determine cleartext (1) protection-level passwords or (2) web-server passwords by leveraging the ability to read these files. | |||||
| CVE-2014-2252 | 1 Siemens | 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more | 2025-04-12 | 6.1 MEDIUM | N/A |
| Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted PROFINET packets, a different vulnerability than CVE-2014-2253. | |||||
| CVE-2016-6486 | 1 Siemens | 1 Sinema Server | 2025-04-12 | 7.2 HIGH | 7.8 HIGH |
| Siemens SINEMA Server uses weak permissions for the application folder, which allows local users to gain privileges via unspecified vectors. | |||||
| CVE-2014-8551 | 1 Siemens | 4 Simatic Pcs7, Simatic Pcs 7, Simatic Tiaportal and 1 more | 2025-04-12 | 10.0 HIGH | N/A |
| The WinCC server in Siemens SIMATIC WinCC 7.0 through SP3, 7.2 before Update 9, and 7.3 before Update 2; SIMATIC PCS 7 7.1 through SP4, 8.0 through SP2, and 8.1; and TIA Portal 13 before Update 6 allows remote attackers to execute arbitrary code via crafted packets. | |||||
| CVE-2014-0224 | 9 Fedoraproject, Filezilla-project, Mariadb and 6 more | 20 Fedora, Filezilla Server, Mariadb and 17 more | 2025-04-12 | 5.8 MEDIUM | 7.4 HIGH |
| OpenSSL before 0.9.8za, 1.0.0 before 1.0.0m, and 1.0.1 before 1.0.1h does not properly restrict processing of ChangeCipherSpec messages, which allows man-in-the-middle attackers to trigger use of a zero-length master key in certain OpenSSL-to-OpenSSL communications, and consequently hijack sessions or obtain sensitive information, via a crafted TLS handshake, aka the "CCS Injection" vulnerability. | |||||
| CVE-2014-4682 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | 5.0 MEDIUM | N/A |
| The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote attackers to obtain sensitive information via an HTTP request. | |||||
| CVE-2014-2249 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | 5.8 MEDIUM | N/A |
| Cross-site request forgery (CSRF) vulnerability on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 and SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allows remote attackers to hijack the authentication of unspecified victims via unknown vectors. | |||||
| CVE-2016-2200 | 1 Siemens | 15 Simatic S7-1500 Cpu Firmware, Simatic S7-1511-1 Pn Cpu, Simatic S7-1511c-1 Pn Cpu and 12 more | 2025-04-12 | 7.8 HIGH | 7.5 HIGH |
| Siemens SIMATIC S7-1500 CPU devices before 1.8.3 allow remote attackers to cause a denial of service (STOP mode transition) via crafted packets on TCP port 102. | |||||
| CVE-2014-2732 | 1 Siemens | 1 Sinema Server | 2025-04-12 | 5.0 MEDIUM | N/A |
| Multiple directory traversal vulnerabilities in the integrated web server in Siemens SINEMA Server before 12 SP1 allow remote attackers to access arbitrary files via HTTP traffic to port (1) 4999 or (2) 80. | |||||
| CVE-2016-9154 | 1 Siemens | 12 Desigo Web Module Pxa30-w0, Desigo Web Module Pxa30-w0 Firmware, Desigo Web Module Pxa30-w1 and 9 more | 2025-04-12 | 5.0 MEDIUM | 7.5 HIGH |
| Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D (All firmware versions < V6.00.046) and Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 for Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U (All firmware versions < V6.00.046) use a pseudo random number generator with insufficient entropy to generate certificates for HTTPS, potentially allowing remote attackers to reconstruct the corresponding private key. | |||||